ELECTRICAL HAZARDS (BUILDING SERVICES and SYSTEMS)
Electrical Service Room
Clearance around electrical service (breaker panel) shall be a minimum of 30"W x 36"D x 78"H.
Electrical panel shall have no openings (missing approved safety covers).
Electrical breaker/fuse(s) shall not be taped in the on position.
Extension Cord
Extension cords shall not be a substitute for permanent wiring.
Extension cords shall not be affixed to structures.
Extension cords shall not extend through walls, ceilings, or floors.
Exposed / Damaged Wiring
Junction Box missing approved cover.
Open-wire splices are prohibited.
Switch(es) damaged/missing approved cover.
Outlet missing approved cover.
Exposed electrical wiring.
Improper electrical wiring of device.
Multi-plug Adapter / Power Strip
Multi-plug adapter(s) are prohibited.
Power strip(s) shall be grounded and be equipped with overcurrent protection.
Power strip shall be directly connected to an electrical outlet (no piggy-backing).
Power strip cords shall not extend through walls, ceilings, floors, under doors, or under floor coverings.
FIRE DEPARTMENT ACCESS (FIRE SERVICE FEATURES)
FIRE HYDRANT
Hydrant is obstructed/hidden.
Hydrant has insufficient circumferential clearance (3 feet minimum).
FIRE LANE
Striping is insufficient and/or needs repainting.
Fire Lane surface in disrepair (i.e. potholes).
Parking in the Fire lane.
PREMISES IDENTIFICATION
Address not properly posted on front and back of building (6" minimum).
Address not properly posted on front and back of suite (3" minimum).
Address numbers not of a contrasting color.
FIRE ALARM SYSTEM
Overdue for Inspection (annual).
Pull is obstructed.
Battery(s) out of date (Sealed Lead-Acid - 5 years).
FIRE SPRINKLER SYSTEM
FIRE DEPARTMENT CONNECTION
FDC cap(s) missing or damaged.
FDC shall remain clear of any obstructions for a minimum of 3 feet (i.e. Fences, trees).
GUAGES
Gauges out of date (5 year replacement or calibration tested).
INSPECTION
Overdue for Inspection (annual).
SPRINKLER HEADS
Head(s) are to be free of any accumulation of paint.
Head(s) obstructed.
SYSTEM / RISER
Access blocked/obstructed to fire sprinkler system.
Failure to maintain Fire Sprinkler System.
Missing/Illegible Hydraulic Nameplate.
System is overdue system flush (every 5 years).
FIRE SUPPRESSION “HOOD” SYSTEM
INSPECTION
Pull at/near a means of egress, 10 to 20 feet from kitchen exhaust system.
K-Class Extinguisher must be mounted and within 30 feet of cooking equipment.
Overdue for Inspection (semi-annual).
Manual Pull Obstructed.
SYSTEM
Insufficient nozzle coverage.
Needs to be cleaned.
Nozzle blow-off caps are missing or damaged.
VENT-A-HOOD
Needs to be professionally cleaned.
Missing filters.
FIRE EXTINGUISHER
ACCESSIBILITY
Hand-held extinguisher shall be installed on hanger/bracket supplied.
Shall be located in conspicuous locations where they will be readily accessible.
Shall not be obstructed or obscured from view.
Top of the extinguisher shall be mounted no higher than 5 feet (40 lbs or less).
INSPECTION
Overdue for Inspection (annual).
Missing Tag.
Extinguisher shall be recharged after any use or as indicated by inspection.
Pressure gauge reading or indicator not in operable range or position.
Safety seal and tamper indicators are not broken or missing.
HYDROSTATIC TEST
CO2 extinguisher required to be hydrostatically tested every 5 years.
Dry chemical (stainless steel) is required to be hydrostatically tested every 12 years.
Wet chemical extinguisher required to be hydrostatically tested every 5 years.
STRUCTURAL (FIRE-RESISTANCE-RATED CONSTRUCTION)
FIRE DOORS and WALLS
Fire Door(s) assembly improperly modified.
Fire Door(s) do not close and latch properly.
Fire Wall (Smoke Barrier) not maintained properly.
CEILINGS
Improper hanging of merchandise or decoration from the ceiling.
Missing or damaged ceiling tiles.
MEANS OF EGRESS
EMERGENCY EXIT EGRESS
EXIT cannot be concealed by curtains, drapes, decoration, or similar materials.
EXIT door cannot have improper locking hardware.
EXIT sign damaged or missing.
EXIT sign not illuminated properly.
Means of egress is blocked/obstructed.
No combustible storage in means of egress.
Emergency lighting shall be electrically powered with battery backup.
EMERGENCY EXIT DOOR(S)
Door shall be set in motion with a maximum of 30 lbs. of force.
Door shall swing to a full-open position with a maximum of 15 lbs. of force.
EXIT door hardware shall be maintained in working condition.
EXIT door cannot have improper locking hardware.
GENERAL PRECAUTIONS AGAINST FIRE
MISCELLANEOUS COMBUSTIBLE MATERIALS STORAGE
Storage of combustible materials shall be orderly.
Storage shall be maintained 2 feet or more below the ceiling (non-sprinkled).
Storage shall be maintained 18 inches or more below the ceiling (sprinkled).
Combustible materials shall not be stored in exits or exit enclosures.
Combustible materials shall not be stored in boiler, mechanical, or electrical rooms.
Storage shall not be stored/displayed beneath overhead projections (non-sprinkled).
Storage in the open shall not exceed 20 feet in height.
Clearance between ignition sources (heaters and combustibles) shall be maintained.
Compresses gas cylinder not properly secured by an appropriate restraint.